 300W Single Output with PFC Function
Features :
HRP-300
series
Universal AC input / Full range Built-in active PFC function, PF>0.95 High efficiency up to 89% (typ.) Withstand 300VAC surge input for 5 seconds Protections: Short circuit / Overload / Over voltage / Over temperature Built-in constant current limiting circuit 1U low profile 41mm Built-in cooling fan ON-OFF control With DC OK signal output Built-in remote sense function 5 years warranty
SPECIFICATION
MODEL DC VOLTAGE RATED CURRENT CURRENT RANGE RATED POWER OUTPUT VOLTAGE ADJ. RANGE HRP-300-3.3 3.3V 60A 0 ~ 60A 198W HRP-300-5 5V 60A 0 ~ 60A 300W 90mVp-p 4.3 ~ 5.8V 2.0% 0.5% 1.0% HRP-300-7.5 7.5V 40A 0 ~ 40A 300W 100mVp-p 6.8 ~ 9V 2.0% 0.5% 1.0% HRP-300-12 12V 27A 0 ~ 27A 324W 120mVp-p 10.2 ~ 13.8V 1.0% 0.3% 0.5% HRP-300-15 15V 22A 0 ~ 22A 330W 150mVp-p 13.5 ~ 18V 1.0% 0.3% 0.5% HRP-300-24 24V 14A 0 ~ 14A 336W 150mVp-p 21.6 ~ 28.8V 1.0% 0.2% 0.5% HRP-300-36 36V 9A 0 ~ 9A 324W 250mVp-p 28.8 ~ 39.6V 1.0% 0.2% 0.5% HRP-300-48 48V 7A 0 ~ 7A 336W 250mVp-p 40.8 ~ 55.2V 1.0% 0.2% 0.5%
RIPPLE & NOISE (max.) Note.2 80mVp-p 2.8 ~ 3.8V VOLTAGE TOLERANCE Note.3 2.5% LINE REGULATION LOAD REGULATION SETUP, RISE TIME HOLD UP TIME (Typ.) 0.5% 1.0% 16ms/230VAC
1000ms, 50ms/230VAC
2500ms, 50ms/115VAC at full load
16ms/115VAC at full load 120 ~ 370VDC PF>0.99/115VAC at full load 86% 88% 88% 87% 88% 89%
VOLTAGE RANGE Note.5 85 ~ 264VAC FREQUENCY RANGE 47 ~ 63Hz POWER FACTOR (Typ.) INPUT EFFICIENCY (Typ.) AC CURRENT (Typ.) INRUSH CURRENT (Typ.) LEAKAGE CURRENT OVERLOAD OVER VOLTAGE PF>0.95/230VAC 80% 5A/115VAC 35A/115VAC
82% 2.5A/230VAC 70A/230VAC
<1.2mA / 240VAC 105 ~ 135% rated output power Protection type : Constant current limiting, recovers automatically after fault condition is removed 6 ~ 7V 9.4 ~ 10.9V 14.4 ~ 16.8V 18.8 ~ 21.8V 30 ~ 34.8V 3.96 ~ 4.62V Protection type : Shut down o/p voltage, re-power on to recover 90 5 5 (TSW1: detect on heatsink of power transistor) for 3.3V,5V,7.5V ; 95 5 for others (TSW2: detect on heatsink of power diod e) 100
41.4 ~ 48.6V
57.6 ~ 67.2V
PROTECTION
OVER TEMPERATURE DC OK SIGNAL FAN CONTROL (Typ.) WORKING TEMP.
FUNCTION
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down PSU turns on : 3.3 ~ 5.6V ; PSU turns off : 0 ~ 1V Load 35 15% or RTH2 -30 ~ +70 50 Fan on (Refer to output load derating curve)
20 ~ 90% RH non-condensing WORKING HUMIDITY ENVIRONMENT STORAGE TEMP., HUMIDITY -40 ~ +85 , 10 ~ 95% RH TEMP. COEFFICIENT 0.03%/ (0 ~ 50 ) VIBRATION 10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes SAFETY STANDARDS WITHSTAND VOLTAGE SAFETY & EMC
(Note 4)
UL60950-1, TUV EN60950-1 approved I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC / 70% RH
ISOLATION RESISTANCE HARMONIC CURRENT EMS IMMUNITY MTBF
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 EMI CONDUCTION & RADIATION Compliance to EN55022 (CISPR22) Class B
Compliance to EN61000-3-2,-3 Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN55024, EN61000-6-2, heavy industry level, criteria A 176K hrs min. MIL-HDBK-217F (25 ) 199*105*41mm (L*W*H) 0.95Kg;15pcs/15.3Kg/0.69CUFT
OTHERS
DIMENSION PACKING
NOTE
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. 5. Derating may be needed under low input voltages. Please check the derating curve for more details.
File Name:HRP-300-SPEC 2009-11-09
300W Single Output with PFC Function
Mechanical Specification
HRP-300
Case No.980A
18 12.5
series
Unit:mm
4-M4 L=6 168.5 168.5
R2 .25
12.25
199 168.5 12.25 42.5 120
1.5 HOLE IN CHASSIS
4.5
18
1
11
2 3 4 5 6 7 LED CN100 SVR
4-M4 L=5
Terminal Pin No. Assignment
Pin No. 1 2 3 Assignment AC/L AC/N FG Assignment Pin No. DC OUTPUT -V 4,5 6,7 DC OUTPUT +V
Connector Pin No. Assignment (CN100) : HRS DF11-08DP-2DS or equivalent
Pin No. Assignment 1,2,4,6 NC DC-OK 3 5 GND +S 7 -S 8 Mating Housing Terminal
17max.
167.5 167.5
12.25 12.25
4-M4 L=6
Block Diagram
I/P
EMI FILTER
ACTIVE INRUSH CURRENT LIMITING
RECTIFIERS & PFC O.T.P.
POWER SWITCHING O.L.P. PWM CONTROL
RECTIFIERS & FILTER DETECTION CIRCUIT O.V.P.
FG PFC CONTROL
Derating Curve
Output Derating VS Input Voltage
Ta = 25
100
100 90
80
80 70
60
LOAD (%)
50 40
LOAD(%)
60 50 40
20
-30
0
10
20
30
40
50
60
70
(HORIZONTAL)
85
100
125
135
155
AMBIENT TEMPERATURE ( )
INPUT VOLTAGE (V) 60Hz
File Name:HRP-300-SPEC 2009-11-09
12.5 18 41
HRS DF11-8DS or equivalent
HRS DF11-**SC or equivalent
15
75 105 125
9.2
FAN
Air flow direction
17
28
fosc : 70KHz
+S +V -V -S DC OK
264


▲Up To Search▲   

 
Price & Availability of HRP-300-12

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X